CG450-1560 CycleGard Low Water Cutoff for Steam Boilers w/ 15 Minute Intermittent Level Test - 120V (45-460-1560)

Part Number: CG450-1560 Brand: Hydrolevel Company

CG450-1560 CycleGard Low Water Cutoff for Steam Boilers w/ 15 Minute Intermittent Level Test - 120V (45-460-1560)

Price
Request a Quote
Stock
In Stock

Intermittent Level Test – Maximum Protection for Foaming Boilers

  • 15 Second Burner Off Delay
  • 30 Second Burner On Delay
  • Automatic Reset
  • Low Water Indicating Light
  • Direct Boiler Mounting – Eliminates Blowdowns Burner circuit contacts open after 15 second delay in a low water condition. Delay prevents short cycling caused by momentary fluctuations in the boiler water level. Automatically reactivates burner circuit 30 seconds after water reaches the probe, allowing optional water feeder to raise water level above the probe. Intermittent Level Test (ILT) feature provides maximum boiler protection by removing power from the burner circuit at set intervals. 

    This model performs the Intermittent Level Tests every 15 minutes for 60 seconds.
  • Replaces CG450-2060
  • Replaces GC450-1090

 

Features

Includes EL1214 Probe

Documentation

show more