The Beckett GeniSys® 7590 Gas Power Burner Control is a safety control designed for use on gas power burners.
This control is intended for use in residential and light commercial gas heating applications.
Applications may include boilers, furnaces, water heaters, space heating and commercial cooking equipment.
The 7590 provides supervision of a separate 120 VAC igniter, a 120 VAC combustion blower motor, a 24 VAC gas valve and 24 VAC connections for an air proving switch (on 7590 C, D).
The control uses flame rectification principles to prove the presence of the burner flame.
Basic diagnostic information is provided through 3 LEDs.
Additional diagnostic information and control setup will be available through the BeckettLink 7700A diagnostic tool.
The Beckett GeniSys® Gas Power Burner Control is a 24 Vac primary safety control designed for use on gas power burners in residential and light commercial gas heating applications.
The GeniSys® Gas Power Burner Control provides supervision of a 120 volt burner motor and a separate 120 Vac igniter as well as a 24 Vac gas valve.
The 7590C and D models provide connections for a combustion air proving switch and monitor the switch position to check for sticking or welded switch contacts.
The standard 7590 is designed for use on applications below 400,000 BTUs. For applications above 400,000 BTUs, contact Beckett’s Engineering Group.
Quick Status Check
3 LEDs provide easy diagnostics for faster troubleshooting and service calls — service personnel can quickly determine control status.
Features- 3 LEDs provide basic diagnostic information
- Single or multiple trials for ignition before lockout
- Designed for easy mounting on a 4 x 4 junction
- Selectable ignition timing 4-15 seconds
- Selectable pre-purge timing 1-240 seconds
- Selectable relight or recycle operation on loss of flame
- The microprocessor is checked for proper operation before each cycle
- Checks combustion air proving switch contacts on 7590C and D models
- Gas valve relay check on each cycle
- Available model (7590C) with manual reset button and non-volatile lockout
- Communication Port links new alarm module and future products
- For use on natural or LP gas
- Provides reliable proof of flame using flame rectification
- Available Lockout Sequences
- D and T Models – Lockout Sequences
- Lockout after single trial for ignition
(volatile lockout) - Lockout with retrial every 1 hour (volatile lockout)
- Lockout after 3 trials for ignition (volatile lockout)
- C Models – Lockout Sequence
- Shutdown after flame failure or failure to light (no relight attempt)
- 5 minute minimum waiting time
- 1 retry attempt allowed, then non-volatile lockout
- Lockout must be manually reset using reset button