Dimensions
- 6-1/8 in. high x 4-3/8 in. wide x 3-1/16 in. deep
- 156 mm high x 111 mm wide x 78 mm deep
Maximum Safe Operating Pressure
- 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
- 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.
Temperature Range
- Maximum: 150° F at switches; 265° F at sensing element
- Maximum: 66° C at switches; 129° C at sensing element
Approvals, Underwriters Laboratories Inc.
- UL Listed (models with well): File MP466, Guide No. MBPR; UL Component Recognized (models without well): File MP466, Guide No. MBPR2
Approvals, Canadian Standards Association
- Certified: File LR1620, Guide No. 400-E-O
Operating Humidity Range
- 0 to 95 % RH, Non-Condensing
Operating Temperature Range
- High Limit: 130° to 240° F adjustable; Low Limit: 110° to 220° F adjustable
- High Limit: 54° to 116° C adjustable; Low Limit: 43° to 104° C adjustable
Differential Temperature
- High limit: 10° F fixed; low limit: 10° to 25° F adj.
Electrical Ratings, Burner
- At Full Load - 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - 44.4 A @ 120 Vac: 22.2 A @ 240 Vac
Electrical Ratings, Circulator