L4006E1067/U Aquastat, Breaks on Rise, 130-270F Range, 250F Factory Stop, Less Well

Part Number: L4006E1067/U Brand: Resideo Technologies Inc

Aquastat, Breaks on Rise, 130-270F Range, 250F Factory Stop, Less Well

Price
Request a Quote
Stock
In Stock
Does not ship to Washington, United States

Aquastat® Controllers from Resideo are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.

L4006 are used in applications that utilize the existing wells
Features
  • Totally Enclosed Micro Switch™ Snap-acting Switches Operate on Temperature Rise to Setpoint.
  • Visible Control Point Scale and External Adjustment Screw Permit Easy Setting.
  • Horizontal or Vertical Insertion of the Sensing Element.
  • Direct or Well Immersion of the Sensing Element.
  • Models Available for Strap-on Mounting.
  • Remote Bulb Model May be Used to Sense Air Temperature in Ducts and in Outside Air Sensing Applications.
  • Models Include Heat-conductive Compound.
  • Select Models Have Wells.
  • UL Limit Rated Device.

Specifications

Hazmat Information

  • UN 1294, TOLUENE, 3, II

Dimensions

  • Case: 5-5/8 in. high x 2 in. wide x 2-1/8 in. deep
  • Case: 143 mm high x 51 mm wide x 54 mm deep

Temperature Range

  • Maximum 150 °F
  • Maximum 66 °C

Includes

  • Heat-conductive compound; Stop factory-set at 250 F (121 C); Well adapter

Mounting

  • Horizontal or Vertical

Electrical Ratings

  • Millivolt - 0.25 A @ 0.25 to 12 Vdc; At Full Load - 8A @ 120 Vac: 5.1A @ 240 Vac; At Locked Rotor - 48A @ 120 Vac: 30.6A @ 240 Vac

Approvals, Underwriters Laboratories Inc.

  • UL Component Recognized: File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2

Approvals, Canadian Standards Association

  • Certified: File No. LR95329-1

Approvals, American Gas Association

  • AGA Certified

Tradeline Value

  • Tradeline

Operating Temperature Range

  • 130 F to 270 F
  • 54 C to 132 C

Bulb Size

  • 10 mm x 73 mm copper
  • 3/8 in. x 2-7/8 in. copper

Differential Temperature

  • Manual Reset

Switching Action

  • SPST, contacts break on temperature rise.

Capillary Length

  • 3 in.
  • 76 mm

  • High Limit; Manual Reset

show more