Dimensions
- 6-1/8 in. high x 4-3/8 in. wide x 3-1/16 in. deep
- 156 mm high x 111 mm wide x 78 mm deep
Maximum Safe Operating Pressure
- 200 psi on outside of immersion well, 100 psi on capsule if inserted directly.
- 1378 kPa on outside of immersion well, 690 kPa on capsule if inserted directly.
Temperature Range
- -30 °F to 150 °F at switches; 265 °F at sensing element
- -34 °C to 66 °C at switches; 129 °C at sensing element
Operating Humidity Range
- 0 to 95% RH, non-condensing
Operating Temperature Range
- High Limit: 130 °F to 240 °F; Low Limit: 110 °F to 220 °F
- High Limit: 54 °C to 116 °C; Low Limit: 43 °C to 104 °C
Differential Temperature
- High limit: 10 °F fixed; low limit: 10 to 25 °F adj.
Electrical Ratings, Burner
- 1.25A at 24 Vac; 30 VA (total load) Terminals B1-B2 and TV-Z
Electrical Ratings, Circulator
- At Full Load - 7.4 A @ 120 Vac: 3.7 A @ 240 Vac; At Locked Rotor - 44.4 A @ 120 Vac: 22.2 A @ 240 Vac