6020002FRS CARLIN UNIVERSAL GAS PRIMARY (REPLACES THE 6020002FR363S & 6020002FR943S)

Part Number: 6020002FRS Brand: Carlin Combustion Technology, Inc

CARLIN UNIVERSAL GAS PRIMARY FOR EZ-GAS, 201GAS, 301GAS & 601GAS

Price
Request a Quote
Stock
In Stock
Does not ship to OH, United States

CARLIN UNIVERSAL GAS PRIMARY

Carlin 60200FRS Flame Rod Gas Burner Primary Control for EZ-Gas, EZ-Gas Pro, 201GAS, 301 GAS and 601GAS Burners. Now with LCD Screen!
Replaces Carlin 6020002FRS, 602000FRS, 60200-02FR, 6020002FR, 602002FR363S, 6020002FR943S
Features
  • On-Board LCD Screen: Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information 
  • Fault History records last 50 fault cycles to aid the technician in troubleshooting 
  • Field Settable Timings 
  • Pre-purge (0, 10, 30, 90) 
  • Trial for Ignition Time (4, 6) 
  • Post-Purge (0, 10, 15, 30, 60, 120) 
  • Number of Recycles allowed (0, 1, 3) 
  • Serviceman Reset Protection (3) 
  • Low Voltage Terminals TT (can be programmed as Used or Not used) Blocked Vent input (contact closure, functions as a low voltage limit) CO input (contact closure) required to start C.F.H .
  • Lockout if not detected during run Alarm output (dry contacts) 24VAC/DC

Documentation

show more